How many volts a cable loses on its way, and which cross-section keeps the limit. The calculation is the one OpenECraft uses for the final circuits of an installation.
Loading the tool. It is the code of the editor, about 10 MB, loaded once.
The tool could not start in this browser. It needs WebAssembly.
How it is calculated
ΔU = k · I · L · (ρ / A · cos φ + x · sin φ)
- k is 2 for a single-phase or DC circuit, where the current flows there and back, and 1.732, the square root of 3, for a three-phase circuit with the voltage between the lines.
- The resistivity is the one of the conductor in operation, 1.25 times its value at 20 °C (IEC 60364-5-52): 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminium.
- The reactance of the cable is taken as 0.08 mΩ per metre. It matters for large cross-sections and a low power factor.
- The limit is yours to set: 3 % is common for lighting and 5 % for other loads, and the regulations of your country decide.
In a project, OpenECraft measures the cable lengths along the installation zones of the rooms and checks every final circuit this way, feeder cables included.
The result supports the planning. A qualified person has to verify it against the standards and regulations that apply.